R8482A-T500
ACOLAN® COPPER
Applications
- 10 Gigabit high speed data transmission cables are designed for horizontal cable distribution local computer networks.
- These cables allow the use of the protocol supported by the class FA for the 10 GBASE-T applications.
- They are characterized of up to 1500 MHz.
- They are compatibles with PoE & PoE+, UPoE & 4PPoE (PoE++) applications.
See our White Paper on installation conditions on www.acome.com also available on demand.
General characteristics
Ìý
|
Solid annealed red copper wire, AWG 22 |
|
Cable assembly in Twisted Pairs |
|
Pet/Alu foil around each pair |
|
4 pairs screening assembly |
|
Tinned copper braid |
|
LSOH-FR : Low Smoke « Zero » Halogen – Flame Retardant |
Ìý
Designation ACOLAN FIREPROTECT | Ref. | Colour | Diameter | Weight | Superior calorific capacity (PCS) | Max pulling tension | |
mm | Kg/km | MJ/km | KWh/m | N | |||
1500 SF-S 4P LSOH-FRÌý | R8481A | Yellow | 7.70 | 57 | 521 | 0,145 | 125 |
1500 SFD-S 4P LSOH-FR | R8482A | Yellow | 7.90 x 16.00 | 124 | 1169 | 0,325 | 250 |
Ìý
Ìý
Characteristics | Values | |
Bending radius | Dynamics (installation) | ≥ 70 mm |
Static (installed) | ≥ 35 mm | |
Temperature range | In service | - 20°C at + 60°C |
At the installation | 0°C at + 50°C | |
Transport and storage | 0°C at + 50°C |
Ìý
Electrical characteristics at 20°C (68°F)
Characteristics | Values | ||
Complete conductor resistance | ≤ 120 ΩÌý/ km | ||
Resistance unbalance | ≤ 2 % | ||
Dielectric strengh | Continuous current | 1kV during 1 minute = no breakdown | |
Insulation resistance | (500 V) | ≥ 5000 MΩÌý. km | |
Capacitance unbalance | Real-ground | ≤ 1200 pF / km | |
Characteristic impedance | at 100 MHz | 100 ±Ìý 5ÌýΩ | |
Velocity | nominal | 78% | |
Coupling attenuation | ≥ 85 dB | TYPE 1b | |
Transfert impedance | atÌý Ìý 1 MHz | ≤Ìý Ìý Ìý10 mΩÌý/ m | GRADE 1 |
atÌýÌý 10 MHz | ≤Ìý Ìý Ìý10 mΩÌý/ m | ||
atÌýÌý 30 MHz | ≤Ìý Ìý20 mΩÌý/ m | ||
at 100 MHz | ≤Ìý Ìý30 mΩÌý/ m | ||
Segregation classification acc. to EN 50174-2 | ‘â¶Ä™d’â¶Ä™ |
Ìý
Frequency (MHz)Ìý | Ìý | 4 | 10 | 20 | 62.5 | 100 | 250 | 300 | 600 | 1000 | 1200 | 1500** |
Attenuation. (dB/100m) | Typical value | 3.4 | 5.2 | 7.4 | 13.4 | 16.8 | 27.4 | 30 | 43.0 | 57.8 | 64.0 | 73.0 |
Imposition (max)* | 3.7 | 5.8 | 8.2 | 14.6 | 18.5 | 29.7 | 32.7 | 47.1 | 61.9 | - |
- |
|
Next (dB) | Typical value | 100 | 100 | 100 | 100 | 100 | 92 | 90 | 87 | 85 | 83 | 80 |
Imposition (min)* | 75 | 75 | 75 | 75 | 73 | 67 | 66 | 61 | 58 | - | - | |
PS Next (dB) | Typical value | 97 | 97 | 97 | 97 | 97 | 89 | 87 | 84 | 82 | 80 | 77 |
Imposition (min)* | 75 | 75 | 75 | 73 | 70 | 64 | 63 | 58 | 55 | Ìý | - | |
ELFEXT (dB/100 m)Ìý | Typical value | 90 | 90 | 85 | 84 | 80 | 72 | 69 | 61 | 56 | 53 | 50 |
Imposition (min)* | 78 | 74 | 68 | 58 | 54 | 46 | 44 | 38 | 34 | - | - | |
PS ELFEXT (dB/100 m)Ìý | Typical value | 87 | 87 | 82 | 81 | 77 | 69 | 66 | 58 | 53 | 50 | 47 |
Imposition (min)* | 75 | 71 | 65 | 55 | 51 | 43 | 41 | 35 | 31 | - | - | |
Return Loss (dB)Ìý | Typical value | 26 | 28 | 28 | 28 | 26 | 24 | 22 | 19 | 18 | 18 | 17 |
Imposition (min)* | 23 | 25 | 25 | 21.5 | 20.1 | 17.3 | 17.3 | 17.3 | 15.1 | - | - |
* Category 7a according IEC 61 156-5 Ed. 2nd
** For information only
Ìý
Norms and standards
Ìý ÌýÌý ÌýÌý ÌýÌý Ìý
Ìý
Applications
IEEE 802.3 :10Base-T; 100Base-TX;1000Base-T; 2,5GBase-T ; Ìý5GBase-T ; 10GBase –T
IEEE 802.3 af (PoE) / 802.3 at (PoE+) / 802.3 bt (4PPoE 90W)
IEEE 802.5 / ÌýFDDI / ATM / RNIS
Cable
IEC 61156-5 ed.2 / ÌýEN 50288-9-1
Cabling system standard
ISO/IEC 11801 2nd ed. / EN 50173-1Ìý
Cabling system installation standards
EN 50174
Directive / Regulation
RoHS 2011/65/UE
REACH 1907/2006/EC
Ìý
Ìý
Europe
Type | Euroclass | Standards | Declaration of performance | |
4P | Dca-s2,d2,a1 | IEC 60332-1, EN 50399,Ìý IEC 60754-2 | 20SFTP018Ìý | |
2x4P | 20SFTP019 |
Ìý
Hors Europe
No flame propagation | IEC 60332-1 / EN 60332-1 |
Low smoke opacity | IEC 61034-2 / EN 61034-2 |
Low gas corrosivity | IEC 60754-2 / EN 60754-2 |
Low toxicity | IEC 60754-1 / EN 60754-1 |
Ìý
Recommendations
Type |
References |
Individual |
Expedition |
||||
TypeÌýÌý |
Weight |
EAN code |
Quantity |
Weight |
EAN code |
||
4P LSOH-FR |
R8481A-T500 |
drum KT of 500 m |
31Ìýkg |
3700223642267 |
12Ìýdrums |
389 kg |
3700223642274 |
R8481A-T1000 |
drum XL of 1000 m |
62Ìýkg |
3700223644384 |
4 drums |
262Ìýkg |
3700223644377 |
|
2 x 4P LSOH-FR |
R8482A-T500 |
drum XL of 500 m |
67Ìýkg |
3700223644278 |
4 drums |
282Ìýkg |
3700223644285 |
Ìý